Transformer manufacturers tell you what to do when the transformer encounters problems?


Release time:

2021-07-08

When the tap changer is regulated, the noise is increased. The DC resistance value of the double-arm bridge is tested, and it exceeds 2% of the original factory data, which is caused by dirt on the contact. When the transformer is running. Sound strength is proportional to the size of the operating voltage and load current. This is the sound of the normal operation of the transformer. If other sounds appear, the transformer is faulty. The 6/0.4KV distribution transformer is analyzed as follows.

 

 

When the tap changer is regulated, the noise is increased. The DC resistance value of the double-arm bridge is tested, and it exceeds 2% of the original factory data, which is caused by dirt on the contact. When the transformer is running. Sound strength is proportional to the size of the operating voltage and load current. This is the sound of the normal operation of the transformer. If other sounds appear, the transformer is faulty. The 6/0.4KV distribution transformer is analyzed as follows.

1. Clear sound of iron strike

This is the high-voltage lead through the transformer oil to the shell discharge, belongs to the insulating oil contains moisture, resulting in insufficient distance to the ground.

Disposal method: Use a clean and dry funnel to add transformer oil that has passed the test from the oil injection hole of the oil conservator, and add the oil replenishment amount to the oil surface line at 20 ℃. If possible, vacuum oiling shall be used to remove air bubbles from the windings.

At this time, if the low-voltage winding is open, there is an output voltage of 1622V, which can also be used as a power supply for eddy current heating in the fuel tank. The method is to connect 1016mm2 plastic aluminum core wires from the abc terminal of the low-voltage winding of the power distribution, and connect them to the neutral terminal of the low-voltage winding of the distribution transformer after winding them for 3 turns on, in and under the oil tank shell respectively. The heat generated by eddy current can uniformly heat the oil tank of the distribution transformer and further improve the drying quality of the distribution transformer.

2. The whispering of the transformer

Disposal method: immediately arrange power outage and maintenance. Generally, it occurs on high-voltage overhead lines, such as the connection between the conductor and the isolating switch, the joint in the tension section, the contact point of the drop fuse and the lower lead connector are broken, loose or in poor contact. After troubleshooting, it can be allowed to be put into operation. 5. The humming sound of the transformer weakens the power transmission after the transformer is shut down or the power transmission after the new installation is completed and put into operation and acceptance. It is often found that the voltage is abnormal, which is caused by the thin high-voltage lead wire, the heating and disconnection in operation, or the fuse blowing and poor contact after long-distance transportation, improper handling or drop fuse. When measuring the voltage on the low voltage side, there will be different values of three-phase voltage and zero Yyn0 connection for one phase, which is caused by two-phase power supply. When running, the alternating magnetic flux generated by the current through the iron core is weakening, so a small buzzing uniform electromagnetic sound is emitted from the transformer.

Test the DC resistance value of the low voltage winding. The abbcca imbalance rate should be within ± 1%. 3 Poor contact of drop-out fuse. Generally occurs in the melter on the upper contact, the reason is not enough pressure caused. The upper contact can be forced to press down by a pull-off lever and contact with the molten core reliably.

Due to changes in load and ambient temperature, the oil surface line of the oil conservator changes. Therefore, water vapor is sucked into the oil conservator along with the air and condenses into water droplets, which promotes internal oxidation and rust. As the build-up level intensifies, the rust will fall to the lower part of the conservator. The rust accumulates on the local iron yoke through the connecting pipe between the oil conservator and the oil cover, thus generating vibration and special noise under the action of electromagnetic force. This will also lead to an increase in mechanical impurities in the transformer operating oil and deteriorate the oil quality.