Dry-type transformer price and maintenance considerations
Release time:
2021-10-08
Even if the price of dry-type transformers is cheap, they need to be overhauled in actual operation and main use. Dry-type transformer in the maintenance process will be found in the operation of various problems. There are many noteworthy problems in the maintenance of dry-type transformers.
Dry-type transformer priceEven if it is cheaper, it needs to be overhauled in actual operation and main use. Dry-type transformer in the maintenance process will be found in the operation of various problems. There are many noteworthy problems in the maintenance of dry-type transformers. In general, dry-type transformer price and maintenance precautions are what? The following are the specific measures and main methods of common dry-type transformer maintenance.
Dry-type transformer price and maintenance considerations:
(1) Check that the display of the dry-type transformer thermostat is normal, start the actual drive of the fan, over-temperature alarm, over-temperature trip, and the action is correct.
(2) After all fans of dry-type transformers are started, the transformer capacity can be increased to 40%-50% of its rated capacity.
(3) No matter how expensive the price of dry-type transformers is, they need to have a certain amount of ventilation to meet the requirements of rated capacity. If it is installed in the basement of a building, ventilation should be strengthened, otherwise the rated capacity or overload capacity will be reduced.
(4) During normal operation, strengthen the monitoring of the temperature display of the dry-type transformer thermostat, and regularly check the fan drive to ensure that the fan starts at any time.
(5)Dry-type transformer priceRegardless of the high or low, pay attention to check whether the epoxy resin poured outside the coil is cracked and whether the room is wet. In the summer rainy season, the exhaust fan should be turned on regularly to keep it dry.
(6) Check that the secondary incoming and outgoing wiring terminals of the dry-type transformer 1. are in good contact without heating or overheating.
(7)Dry-type transformerThe external insulation shall be cleaned by power failure at least once a year to keep its surface clean and reduce leakage.
Dry-type transformer price expensive in the installation and commissioning:
1. Unpacking inspection before installation
Check that the packaging is intact. After the transformer is unpacked, check whether the transformer nameplate data meets the design requirements, whether the factory documents are complete, whether the transformer is in good condition, whether there are signs of external damage, whether the parts are shifted or damaged, whether the electrical bracket or connecting line is damaged, and check whether the spare parts are damaged and short.
2. Transformer installation
First check the transformer foundation and check whether the embedded steel plate is horizontal. There should be no holes under the steel plate to ensure that the transformer foundation has good seismic and sound absorption performance, otherwise the noise of the installed transformer will increase. Then the transformer is moved to the installation position with the roller, the roller is removed, and the transformer is accurately adjusted to the design position, and the installation level error meets the design requirements. Four short channel steels, I .e. embedded steel plates, are welded on the four corners near the base of the transformer so that the transformer will not move during use.
3.Dry-type transformerWiring
When wiring, the distance between the charged bodies and between the charged body and the ground should be guaranteed to be small, especially the distance between the cable and the high-voltage coil. The high current and low voltage busbars shall be separately supported and shall not be directly crimped on the transformer terminals to generate excessive mechanical tension and torque.