Analysis of the use of oil-immersed transformers


Release time:

2022-04-26

Oil-immersed transformer suppliers summarize and introduce the fire safety measures for oil-immersed transformers as follows: between oil-immersed transformers with an oil content of more than 2500kg and oil-filled electrical equipment with an oil content of 600kg-2500kg, the fire distance shall not be less than 5m. If the fire distance between two adjacent oil-immersed transformers is small and cannot meet the fire protection requirements, a fire partition wall or a fire water curtain must be added on the top of the fire partition wall.

Oil-immersed transformer suppliers summarize and introduce the fire safety measures for oil-immersed transformers as follows: between oil-immersed transformers with an oil content of more than 2500kg and oil-filled electrical equipment with an oil content of 600kg-2500kg, the fire distance shall not be less than 5m. If the fire distance between two adjacent oil-immersed transformers is small and cannot meet the fire protection requirements, a fire partition wall or a fire water curtain must be added on the top of the fire partition wall.

 

When the oil-immersed transformer is installed outdoors, when the distance between the outer edge of the oil-immersed transformer and the adjacent wall is less than 0.8m, the wall shall be firewalled. When the oil-immersed transformer is installed outdoors, when the wall surface is within 5m from the outer edge of the oil-immersed transformer, the total thickness of the transformer plus 3m below the horizontal line and the outer edges on both sides plus 3m each.

Doors, windows and holes shall not be opened; doors and fixed windows on walls outside their scale shall have a fire resistance limit of not less than 0.9h. Oil-immersed transformers shall be equipped with fixed water spray and other rescue systems as required by relevant standards and rules. If the oil-immersed transformer is installed in a separate room.

The door of the room should be a Class B fire door that opens outward and leads to the outside of the house or corridor, and should not open to other rooms. Oil-immersed transformer is an important power system in the important power equipment, so it is particularly important to do a good job in the safety of oil-immersed transformers and to ensure the safety of oil-immersed transformers.