Notes on the purchase of oil-immersed transformers
Release time:
2022-05-31
Under normal circumstances, when purchasing and mounting oil-immersed transformers, whether the oil-immersed transformers are to be mounted indoors or in the wild, their altitude shall not exceed 1000 meters, the temperature shall not exceed 40 degrees Celsius, and the daily average temperature shall be controlled at about 30 degrees Celsius. the annual average temperature is 20 to -25 degrees Celsius.
Under normal circumstances, when purchasing and mounting oil-immersed transformers, whether the oil-immersed transformers are to be mounted indoors or in the wild, their altitude shall not exceed 1000 meters, the temperature shall not exceed 40 degrees Celsius, and the daily average temperature shall be controlled at about 30 degrees Celsius. the annual average temperature is 20 to -25 degrees Celsius.

Oil-immersed transformers. During normal operation of oil-immersed transformer, if the oil quantity is more than 2500kg, the fire distance between oil-filled electrical equipment with oil quantity of 600kg-2500kg shall not be less than 5 m. If the distance between two adjacent oil-immersed transformers does not meet the requirements of the device, it is also necessary to set up a firewall or fire water curtain on the top of the fire partition wall. For single-phase oil-immersed pressure transformer equipment, only fireproof partition wall or fireproof water curtain can be set up.
When the oil-immersed transformer is installed in the plant, the interval between the outer edge of the transformer and the outer wall shall not be less than 0.8 m, and the outer wall shall be equipped with firewall. When the distance between the outer wall of the factory building and the outer edge of the oil-immersed transformer is within 5 meters, do not open doors, windows and holes within the scale below the horizontal line of the total thickness of the transformer plus 3m and within the scale of 3m on the outer edges of both sides.
For doors and fixed windows on firewalls outside their scale, the fire limit should not be less than 0.9h. If there is a device condition, the oil-immersed transformer can be installed in a separate room, and a fixed water spray and other rescue system can be set. In addition, the door of the room should be a Class B fire door that opens outward and leads to the outside of the house or corridor, but not to other rooms.