In the use of dry-type transformers, there will always be faults of one kind or another, and there are many types of faults in dry-type transformers. What are the common faults of dry-type transformers? How to solve them? Let's take a look.

In the use of dry-type transformers, there will always be faults of one kind or another, and there are many types of faults in dry-type transformers. What are the common faults of dry-type transformers? How to solve them? Let's take a look.

Abnormal temperature rise of 1. transformer

Dry-type transformer operation is abnormal mainly in terms of temperature and noise. If the temperature is abnormally high, the specific treatment measures and steps are as follows:

1. Check whether the thermostat and thermometer are out of order;

2. Check whether the blower and indoor ventilation are normal;

3. Check the load of the transformer and the insertion of the thermostat probe to eliminate the failure of the thermostat and the fan. Under normal load conditions, the temperature will continue to rise. It should be confirmed that there is a fault in the transformer, and it should be shut down for maintenance. The reasons for the abnormal temperature rise are:

1. Transformer winding partial stratification or turn-to-turn short circuit, internal contacts loose, contact resistance increased, short circuit on the secondary line, etc;

2. The transformer core is locally short-circuited, and the insulation of the core-piercing screw is damaged;

3. Long-term overload operation or accident overload;

4. Deterioration of heat dissipation conditions, etc.

Treatment of Abnormal Sound of 2. Transformer

Do you understand the price of dry-type transformers? Transformer sound is divided into normal sound and abnormal sound. The normal sound is the "buzzing" sound from the transformer excitation, which varies with the load. When abnormal sound occurs in the transformer, first analyze and judge whether the sound is inside or outside the transformer.

If internal, the possible components are:

1. If the core is not clamped and loose, it will make a "jingle" sound;

2. If the iron core is not grounded, it will emit a slight discharge sound of "crackling" and "crackling;

3. Poor contact of the switch will cause "squeaking" and "crackling", and it will become larger as the load increases;

4. When the oil on the surface of the shell is serious, it will make a "hissing" sound.

If external, the possible parts are:

1. Overload operation will make a heavy "buzzing sound";

2, the voltage is too high, the transformer sound is loud and sharp;

3. When the phase is open, the sound of the transformer is sharper than usual;

4. When magnetic resonance occurs in the power grid system, the transformer will emit uneven noise;

5. When the low-voltage side is short-circuited or grounded, the transformer will make a huge "bang" sound;

6. When the external connection is loose, there is an arc or spark.

5. Simple treatment of temperature control fault.

3. iron core has low insulation resistance to ground.

This is mainly due to the high humidity of the ambient air, which leads to low insulation resistance of dry-type transformers.

Solution: Place the iodine tungsten lamp under the low-voltage coil and bake continuously for 12 hours. As long as the insulation resistance of the iron core and the high and low voltage coils is low due to moisture, the insulation resistance value will increase accordingly.

The insulation resistance of the 4. iron core to the ground is zero.

Explain that the connection between metals may be due to burrs, metal wires, etc. The paint is brought into the core, and the two ends are overlapped between the core and the wire clamp. The insulation damage of the foot causes the iron core to be connected to the foot; the metal falls into the low-voltage coil, causing the pull plate to be connected to the iron core.

Solution: Use lead wire to poke down the channel between the low-voltage coil core stages, and check the insulation of the foot after confirming that there is no foreign matter.