Dry-type transformer manufacturers tell you the common fault problems of dry-type transformers


Release time:

2021-07-21

In the process of using dry-type transformers for a long time, it is easy to have some fault problems. In order to reduce some unnecessary troubles caused by these problems, we need to carry out timely maintenance on dry-type transformers, so we should constantly sum up experience. Here we will take a look at some common fault problems and solutions in the process of using dry-type transformers.

In the process of using dry-type transformers for a long time, it is easy to have some fault problems. In order to reduce some unnecessary troubles caused by these problems, we need to carry out timely maintenance on dry-type transformers, so we should constantly sum up experience. Here we will take a look at some common fault problems and solutions in the process of using dry-type transformers.

1. When the dry-type transformer winding is short-circuited, the resulting phenomenon is that the temperature of the dry-type transformer is too high, there is a burning smell, smoke, reduced output voltage, unstable output voltage, etc. If these phenomena are found, the power supply should be cut off immediately for inspection. The main reasons for the short circuit are: due to the dry-type transformer damp internal mildew, the insulation layer will be damaged for a long time, resulting in serious leakage or short circuit; or due to the dry-type transformer insulation material aging, insulation performance is reduced, causing insulation breakdown, resulting in short circuit. In addition, a sudden increase in power supply voltage can also cause insulation breakdown and winding short circuit.

2. When the dry-type transformer is open, there is no output voltage, and the primary input current is small or no input current. The main reasons for the open circuit are: the external lead wire is broken; The lead wire and the welding piece are de-welded; The wire package is broken by collision and internal mold is broken after being affected with damp.

3. After finding the cause of the failure of the dry-type transformer, it can be repaired. For external faults, if the wire is broken or de-soldered, the wire can be re-soldered and replaced. If the insulation is burnt due to ignition between the lead wire terminal and the iron core or ignition between the terminals, the distance between the terminal and the iron core or the terminal and the terminal shall be properly pulled apart. If the insulating layer is burnt, the burnt part shall be replaced or removed and sealed with epoxy resin glue.

4. For dry-type transformers with short circuit or large no-load loss due to moisture, if the coil has been short-circuited, the short-circuited wire package should be removed and rewound. Generally, dry-type transformers that have not been short-circuited due to moisture should not be energized to avoid breakdown of the insulating layer. They can be dried in a drying oven to restore their insulation performance.

5. If the no-load loss is large, but the insulation resistance (between the coils, between the coils and the buckle core) is normal, the quality of the core may be poor, the iron loss is large, or the coil has a local short circuit. The short-circuit tester can be used for inspection, and the fault can be eliminated before continuing to use. If it is found that there is a disconnection, short circuit and other faults in the dry-type transformer, the dry-type transformer can be disassembled for repair according to the following steps:

Remove the core 1. Dry-type transformers are often filled with asphalt, wax and other materials. Before disassembly, they should be heated to melt away from the dry-type transformer. In addition, the lead wire of the dry-type transformer should be welded off the terminal, the fixing splint should be removed, a piece of silicon steel sheet should be pryed up with a screwdriver, and then the silicon steel sheet should be pulled out one by one with pliers. When taking out the silicon steel sheet, be careful not to damage the coil lead, and at the same time avoid breaking and bending the silicon steel sheet. Then, collect the removed silicon steel sheets together and wrap them in paper to avoid loss and damage to the insulation.

Remove the coil 2. After taking out the core, first check the appearance of the coil to see that there is no damage to the appearance, and then use the insulation resistance meter to check which coil the fault occurs in, so as to disassemble it purposefully. Note the interlayer insulation, wire diameter, number of turns per layer and number of layers, etc. during disassembly for reference during rewinding. At the same time, attention should be paid to protect the skin of the wire insulation paint for reuse; special attention should be paid to finding and discovering the cause of the coil short circuit and open circuit. When the fault location is found and processed, it can be re-wound according to the original winding method, and carefully tested and inspected after winding and repair. To be in the indicators are in line with the requirements, can continue to use.












 