Oil-immersed transformer: oil-immersed transformer fire safety measures


Release time:

2021-05-21

1. Between oil-immersed transformer with oil quantity above 2500kg and oil-filled electrical equipment with oil quantity between 600kg and 2500kg, the fire distance shall not be less than 5m. 2. The transformer manufacturer reminds that when the fire prevention distance between two adjacent oil-immersed transformers does not meet the requirements, a fire partition wall or a fire water curtain should be added on the top of the fire partition wall. Only fireproof partition wall or fireproof water curtain can be set between single-phase oil-immersed transformers.



1. Between oil-immersed transformer with oil quantity above 2500kg and oil-filled electrical equipment with oil quantity between 600kg and 2500kg, the fire distance shall not be less than 5m.

2. The transformer manufacturer reminds that when the fire prevention distance between two adjacent oil-immersed transformers does not meet the requirements, a fire partition wall or a fire water curtain should be added on the top of the fire partition wall. Only fireproof partition wall or fireproof water curtain can be set between single-phase oil-immersed transformers.

3. When the distance between the outer wall of the plant and the outer edge of the oil-immersed transformer outside the plant is less than that specified in the specification table, the outer wall shall be firewalled. The distance between the wall and the outer edge of the transformer shall not be less than 0.8m.

4. When the outer wall of the factory building is within 5m from the outer edge of the oil-immersed transformer, doors, windows and holes shall not be opened below the horizontal line of the total thickness of the transformer plus 3m and within the range of 3m on the outer edges of both sides. The fire resistance limit of doors and fixed windows on the firewall outside its scope shall not be less than 0.9h.

5. When the oil volume of a single oil-filled transformer and other oil-filled electrical equipment is above 1000Kg, an oil storage pit and a common oil collection pool shall be set up, and transformer pebbles shall be placed for fire prevention and oil unloading.

6. Oil-immersed transformers shall be equipped with fixed water spray and other fire extinguishing systems according to the current relevant specifications. Oil-immersed plant transformers shall be installed in a separate room, and the door of the room shall be a Class B fire door opened outward, and shall be directly connected to the outside of the house or corridor, and shall not be opened to other rooms.