Dry type transformer price: what are the ways of protection of dry type transformer?


Release time:

2022-08-22

Dry-type transformers are used in many fields, such as local lighting. In the previous article on dry-type transformers, the performance characteristics of dry-type transformers. In order to improve people's understanding of dry-type transformers, this article will introduce the protection methods, cooling methods and maintenance methods of dry-type transformers. so dry type transformer price: what are the ways of protection of dry type transformer?

dry type transformer price: what are the ways of protection of dry type transformer?

Dry-type transformers are used in many fields, such as local lighting. In the previous article on dry-type transformers, the performance characteristics of dry-type transformers. In order to improve people's understanding of dry-type transformers, this article will introduce the protection methods, cooling methods and maintenance methods of dry-type transformers. so dry type transformer price: what are the ways of protection of dry type transformer?

dry type transformer price: what are the ways of protection of dry type transformer?

1. Quick-break protection Quick-break protection is to overcome the problem of long action time of overcurrent protection in the protection device near the power supply end, and to protect the line by increasing the setting value and limiting the action range. There are three types of protection: voltage quick-break protection, current quick-break protection and transformer differential quick-break protection.

2. Over-current protection Many electronic devices have a rated current, which is not allowed to exceed, otherwise the equipment will be burned. Therefore, some devices are made into current protection modules. When the current exceeds the set current, the equipment is automatically powered off to protect the equipment.

3. Zero sequence protection Zero sequence protection refers to the occurrence of zero sequence current, zero sequence voltage and zero sequence power after a ground fault occurs in a grounding system with large short-circuit current. Relay protection devices that use these electrical quantities to protect against short circuit to ground are collectively referred to.

dry type transformer price: dry type transformer cooling method is what?

1. When the temperature of the dry-type transformer exceeds the insulation withstand temperature, the insulation will be damaged, affecting the safe operation and service life of the dry-type transformer. Therefore, dry-type transformers should be equipped with suitable cooling devices to keep the winding temperature within the allowable range. Common cooling methods for dry-type transformers include natural air cooling and forced air cooling. The rated capacity of dry-type transformer is natural air cooling capacity, and the output capacity of forced air cooling dry-type transformer can be increased by 40% ~ 50%, which can be used for intermittent overload operation or emergency overload operation.

2. The forced air cooling fan is generally installed in the lower part of the dry-type transformer. Due to the increase of load loss and impedance voltage during overload, it is in a non-economic operation state and should not be overloaded continuously for a long time. Thermistors are installed in the windings of dry-type transformers to measure temperature. When the temperature exceeds the alarm value, an over-temperature alarm signal will be issued. If the temperature continues to rise to the trip value, an overheat trip signal will be issued to trip the dry-type transformer.

Dry-type transformer price: What is the maintenance method of dry-type transformer?

1. Put the standby transformer into operation, disconnect the circuit breaker on the low-voltage side of the transformer for maintenance, remove the control power supply for safe operation, and hang the "No Closing" sign at the switch handle.

2. Disconnect the circuit breaker on the high voltage side of the maintenance transformer, close the grounding switch, fully discharge the transformer, lock the high voltage cabinet, and hang the "No Closing" sign at the switch handle.

3. During the maintenance of dry-type transformer, the porcelain sleeve and casing should be cleaned first, and then the casing, gasket and porcelain sleeve should be checked for cracks, discharge traces or aging of the rubber pad, and whether the cable and bus are deformed. If there is a crack, it should be replaced.

4. Check whether the bus contact surface is clean. The contact surface should be cleaned of oxide layer and coated with power compound grease.

5. Check whether the transformer grounding is good, whether the grounding wire is corroded, and replace the severely corroded ones.

6. Tighten the lead terminals, pins, grounding screws and connecting busbar screws. If it is loose, remove the screw, or gently file the contact surface with a fine flat file, or replace the spring washer and screw until the contact is good.

7. Clean the dust around the transformer and accessories, and check whether the fire fighting facilities and ventilation system are in good condition.

8. Disconnect the high-voltage side grounding switch, lock the high-voltage comb, and measure the insulation resistance with a 2500V shaking meter. Compared with the measured value of the transformer before leaving the factory, the insulation resistance should not be less than 70% of the original data before leaving the factory. Unqualified, should be reported in a timely manner.

9. Once again close the high-voltage side of the grounding switch, let the transformer discharge.

10. Check whether there are tools missing in the power distribution room and transformer, and evacuate from the site.

11. Connect the low-voltage side circuit breaker to control the safe operation of the power supply, and re-hang the "No Closing" sign to prevent reverse power transmission to the transformer.

12. Disconnect the grounding switch on the high-voltage side, check the transformer site and the control line on the low-voltage side again, close the circuit breaker on the high-voltage side of the transformer, and let the transformer run and remove the high-voltage side sign.

13. Make detailed maintenance and commissioning records.

dry type transformer price: dry type transformer safety measures are what?

1. Shake the insulation resistance by two people.

2. Do not touch the transformer before charging and discharging the transformer.

3. Prevent reverse transmission to and from the transformer to the running bus.

4. Maintenance personnel should wear insulated shoes and gloves for operation.

5. Do not drive by mistake.